BC/BD-t-363AA5-B19 C
77.89 kW
Defrost: None
Product code: BC/BD-2x180CC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 18,934 m³/h |
|---|---|
| External surface | 480.2 m² |
| Inner volume | 59.6 dm³ |
| Fin material | Aluminium |
| Net weight | 439 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-2x180CC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 47.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 77.86 | 47.17 | not rated | not rated | not rated | not rated |
| 45 | 107.62 | 77.57 | 47.16 | not rated | not rated | not rated |
| 50 | 137.08 | 107.10 | 77.33 | 47.16 | not rated | not rated |
| 55 | 166.41 | 136.34 | 106.67 | 77.17 | 47.21 | not rated |
| 60 | 195.66 | 165.46 | 135.73 | 106.36 | 77.10 | 47.31 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 36.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 59.49 | 36.40 | not rated | not rated | not rated | not rated |
| 45 | 81.81 | 59.24 | 36.37 | not rated | not rated | not rated |
| 50 | 103.90 | 81.37 | 59.03 | 36.36 | not rated | not rated |
| 55 | 125.88 | 103.29 | 81.01 | 58.88 | 36.39 | not rated |
| 60 | 147.80 | 125.09 | 102.78 | 80.75 | 58.82 | 36.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 77.857 | 13.50 | 59.0 |
| Low speed (Y) | 59.491 | 10.32 | 36.6 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2400 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.