Skip to Content

Dry cooler BC/BD-2x180KC5-B03 C

Dry cooler BC/BD-2x180KC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x180KC5-B03 C

Heat rejection i
68.88 kW
Air flow
19,379 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 19,379 m³/h
External surface 302.6 m²
Inner volume 44.7 dm³
Fin materialAluminium
Net weight 390 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x180KC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
68.883 kW Fluid flow 11.96 m³/h Pressure drop 33.5 kPa
Heat rejection · Low speed (Y)
53.522 kW Fluid flow 9.28 m³/h Pressure drop 21.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 40.65 not rated not rated not rated not rated not rated
40 68.88 40.76 not rated not rated not rated not rated
45 96.30 68.77 40.85 not rated not rated not rated
50 123.47 96.01 68.68 40.95 not rated not rated
55 150.52 123.00 95.77 68.63 41.06 not rated
60 177.51 149.89 122.62 95.60 68.64 41.20

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 31.80 not rated not rated not rated not rated not rated
40 53.52 31.90 not rated not rated not rated not rated
45 74.54 53.42 31.97 not rated not rated not rated
50 95.35 74.30 53.34 32.05 not rated not rated
55 116.05 94.96 74.10 53.31 32.15 not rated
60 136.69 115.53 94.65 73.97 53.32 32.27

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 68.883 11.96 33.5
Low speed (Y) 53.522 9.28 21.3

Dimensions

Dimension drawing of BC/BD-2x180KC5-B03 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 2260 mm
K 2400 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.