Dry cooler BC/BD-2x180KD1-B03 C

Dry cooler BC/BD-2x180KD1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x180KD1-B03 C

Heat rejection i
76.09 kW
Air flow
18,201 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 18,201 m³/h
External surface 446.5 m²
Inner volume 53.3 dm³
Fin materialAluminium
Net weight 422 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class B
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x180KD1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
76.089 kW Fluid flow 13.19 m³/h Pressure drop 29.2 kPa
Heat rejection · Low speed (Y)
57.680 kW Fluid flow 10.00 m³/h Pressure drop 17.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 45.94 not rated not rated not rated not rated not rated
40 76.09 46.01 not rated not rated not rated not rated
45 105.21 75.88 46.08 not rated not rated not rated
50 134.00 104.77 75.71 46.16 not rated not rated
55 162.63 133.35 104.42 75.62 46.27 not rated
60 191.18 161.78 132.82 104.19 75.62 46.44

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 35.10 not rated not rated not rated not rated not rated
40 57.68 35.15 not rated not rated not rated not rated
45 79.39 57.48 35.19 not rated not rated not rated
50 100.83 79.00 57.31 35.24 not rated not rated
55 122.16 100.27 78.68 57.21 35.31 not rated
60 143.41 121.43 99.81 78.46 57.18 35.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 76.089 13.19 29.2
Low speed (Y) 57.680 10.00 17.8

Dimensions

Dimension drawing of BC/BD-2x180KD1-B03 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 2260 mm
K 2400 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.