BC/BD-450CD1-B09 C
83.34 kW
Defrost: None
Product code: BC/BD-2x180MC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 20,517 m³/h |
|---|---|
| External surface | 489.9 m² |
| Inner volume | 57.5 dm³ |
| Fin material | Aluminium |
| Net weight | 471 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-2x180MC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 50.50 | not rated | not rated | not rated | not rated | not rated |
| 40 | 83.17 | 50.41 | not rated | not rated | not rated | not rated |
| 45 | 114.92 | 82.78 | 50.33 | not rated | not rated | not rated |
| 50 | 146.37 | 114.26 | 82.45 | 50.29 | not rated | not rated |
| 55 | 177.68 | 145.45 | 113.69 | 82.19 | 50.29 | not rated |
| 60 | 208.91 | 176.50 | 144.66 | 113.26 | 82.05 | 50.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 39.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 65.04 | 39.74 | not rated | not rated | not rated | not rated |
| 45 | 89.52 | 64.75 | 39.70 | not rated | not rated | not rated |
| 50 | 113.75 | 89.04 | 64.52 | 39.68 | not rated | not rated |
| 55 | 137.88 | 113.08 | 88.63 | 64.35 | 39.70 | not rated |
| 60 | 161.94 | 137.02 | 112.51 | 88.32 | 64.25 | 39.77 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 83.171 | 14.42 | 59.2 |
| Low speed (Y) | 65.037 | 11.28 | 38.2 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2260 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.