Skip to Content

Dry cooler BC/BD-2x180NB1-B03 C

Dry cooler BC/BD-2x180NB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x180NB1-B03 C

Heat rejection i
81.65 kW
Air flow
21,107 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 21,107 m³/h
External surface 494.2 m²
Inner volume 61.9 dm³
Fin materialAluminium
Net weight 479 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class B
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x180NB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
81.645 kW Fluid flow 14.16 m³/h Pressure drop 72.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
65.042 kW Fluid flow 11.28 m³/h Pressure drop 48.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 49.18 not rated not rated not rated not rated not rated
40 81.65 49.12 not rated not rated not rated not rated
45 113.26 81.30 49.06 not rated not rated not rated
50 144.59 112.66 81.00 49.02 not rated not rated
55 175.79 143.74 112.14 80.77 49.01 not rated
60 206.92 174.70 143.01 111.73 80.63 49.06

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 39.50 not rated not rated not rated not rated not rated
40 65.04 39.43 not rated not rated not rated not rated
45 89.86 64.74 39.37 not rated not rated not rated
50 114.44 89.34 64.47 39.29 not rated not rated
55 138.91 113.72 88.89 64.20 39.23 not rated
60 163.32 137.99 113.09 88.45 63.99 39.21

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 81.645 14.16 72.2
Low speed (Y) 65.042 11.28 48.3

Dimensions

Dimension drawing of BC/BD-2x180NB1-B03 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 2500 mm
H 2400 mm
I 2310 mm
K 3050 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.