BC/BD-t-580GC5-B03 C
152.20 kW
Defrost: None
Product code: BC/BD-2x180NC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,189 m³/h |
|---|---|
| External surface | 658.7 m² |
| Inner volume | 86.1 dm³ |
| Fin material | Aluminium |
| Net weight | 534 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x180NC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 152.26 | 90.28 | not rated | not rated | not rated | not rated |
| 45 | 212.66 | 151.82 | 90.35 | not rated | not rated | not rated |
| 50 | 272.50 | 211.74 | 151.44 | 90.42 | not rated | not rated |
| 55 | 332.07 | 271.12 | 210.95 | 151.15 | 90.55 | not rated |
| 60 | 391.49 | 330.25 | 269.95 | 210.35 | 151.02 | 90.76 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 70.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 118.39 | 70.91 | not rated | not rated | not rated | not rated |
| 45 | 164.50 | 117.99 | 70.94 | not rated | not rated | not rated |
| 50 | 210.12 | 163.72 | 117.66 | 70.97 | not rated | not rated |
| 55 | 255.53 | 208.98 | 163.06 | 117.42 | 71.07 | not rated |
| 60 | 300.81 | 254.04 | 208.02 | 162.56 | 117.31 | 71.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 152.264 | 26.40 | 61.2 |
| Low speed (Y) | 118.392 | 20.53 | 39.1 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 2310 mm |
| K | 3050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |