BC/BD-463CC1-B01 C
119.14 kW
Defrost: None
Product code: BC/BD-2x191EB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,882 m³/h |
|---|---|
| External surface | 288.3 m² |
| Inner volume | 48.4 dm³ |
| Fin material | Aluminium |
| Net weight | 382 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x191EB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 67.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 119.15 | 67.92 | not rated | not rated | not rated | not rated |
| 45 | 169.84 | 119.37 | 68.33 | not rated | not rated | not rated |
| 50 | 220.23 | 169.88 | 119.61 | 68.70 | not rated | not rated |
| 55 | 270.48 | 220.09 | 169.97 | 119.87 | 69.08 | not rated |
| 60 | 320.64 | 270.16 | 220.04 | 170.13 | 120.18 | 69.47 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 95.81 | 55.10 | not rated | not rated | not rated | not rated |
| 45 | 136.00 | 95.99 | 55.42 | not rated | not rated | not rated |
| 50 | 175.89 | 136.02 | 96.17 | 55.72 | not rated | not rated |
| 55 | 215.66 | 175.77 | 136.08 | 96.38 | 56.04 | not rated |
| 60 | 255.35 | 215.40 | 175.73 | 136.22 | 96.65 | 56.37 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 119.145 | 20.68 | 83.1 |
| Low speed (Y) | 95.810 | 16.63 | 56.5 |
| A | 1750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1500 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 2050 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.