Skip to Content

Dry cooler BC/BD-2x191KB1-B04 C

Dry cooler BC/BD-2x191KB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x191KB1-B04 C

Heat rejection i
107.78 kW
Air flow
48,151 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 48,151 m³/h
External surface 214.3 m²
Inner volume 38.7 dm³
Fin materialAluminium
Net weight 356 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x191KB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
107.781 kW Fluid flow 18.71 m³/h Pressure drop 31.0 kPa
Heat rejection · Low speed (Y)
86.279 kW Fluid flow 14.98 m³/h Pressure drop 20.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.99 not rated not rated not rated not rated not rated
40 107.78 59.73 not rated not rated not rated not rated
45 155.50 108.27 60.39 not rated not rated not rated
50 202.91 155.80 108.71 60.96 not rated not rated
55 250.17 203.05 156.10 109.15 61.50 not rated
60 297.36 250.16 203.22 156.44 109.60 62.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 47.50 not rated not rated not rated not rated not rated
40 86.28 48.13 not rated not rated not rated not rated
45 124.03 86.67 48.67 not rated not rated not rated
50 161.47 124.26 87.03 49.16 not rated not rated
55 198.78 161.57 124.50 87.39 49.62 not rated
60 236.00 198.75 161.71 124.78 87.78 50.06

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 107.781 18.71 31.0
Low speed (Y) 86.279 14.98 20.8

Dimensions

Dimension drawing of BC/BD-2x191KB1-B04 C
Dimension drawing
Dimensions as drawn
A 1750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1500 mm
H 1400 mm
I 2260 mm
K 2050 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2050 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.