BC/BD-563BB5-B01 C
112.90 kW
Defrost: None
Product code: BC/BD-2x191LB5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 52,517 m³/h |
|---|---|
| External surface | 226.9 m² |
| Inner volume | 43.9 dm³ |
| Fin material | Aluminium |
| Net weight | 385 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 93.4 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x191LB5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 62.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 112.94 | 63.55 | not rated | not rated | not rated | not rated |
| 45 | 161.89 | 113.25 | 64.03 | not rated | not rated | not rated |
| 50 | 210.54 | 162.00 | 113.53 | 64.46 | not rated | not rated |
| 55 | 259.06 | 210.48 | 162.12 | 113.80 | 64.86 | not rated |
| 60 | 307.50 | 258.82 | 210.45 | 162.28 | 114.11 | 65.27 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 51.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 91.84 | 51.96 | not rated | not rated | not rated | not rated |
| 45 | 131.26 | 92.09 | 52.38 | not rated | not rated | not rated |
| 50 | 170.39 | 131.35 | 92.33 | 52.75 | not rated | not rated |
| 55 | 209.40 | 170.34 | 131.46 | 92.58 | 53.10 | not rated |
| 60 | 248.34 | 209.21 | 170.34 | 131.61 | 92.85 | 53.45 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 112.938 | 19.60 | 39.9 |
| Low speed (Y) | 91.840 | 15.94 | 27.6 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2400 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.