Skip to Content

Dry cooler BC/BD-2x191LD5-B04 C

Dry cooler BC/BD-2x191LD5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x191LD5-B04 C

Heat rejection i
150.89 kW
Air flow
47,887 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 47,887 m³/h
External surface 378.2 m²
Inner volume 61.0 dm³
Fin materialAluminium
Net weight 432 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x191LD5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
150.889 kW Fluid flow 26.19 m³/h Pressure drop 82.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
116.845 kW Fluid flow 20.28 m³/h Pressure drop 52.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 88.06 not rated not rated not rated not rated not rated
40 150.89 88.38 not rated not rated not rated not rated
45 212.24 150.87 88.69 not rated not rated not rated
50 273.11 211.92 150.90 88.99 not rated not rated
55 333.76 272.51 211.72 151.01 89.33 not rated
60 394.28 332.88 272.09 211.66 151.23 89.72

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 68.78 not rated not rated not rated not rated not rated
40 116.85 69.05 not rated not rated not rated not rated
45 163.63 116.83 69.29 not rated not rated not rated
50 210.00 163.39 116.85 69.54 not rated not rated
55 256.19 209.54 163.22 116.95 69.82 not rated
60 302.27 255.51 209.21 163.19 117.15 70.16

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 150.889 26.19 82.2
Low speed (Y) 116.845 20.28 52.2

Dimensions

Dimension drawing of BC/BD-2x191LD5-B04 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 2260 mm
K 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.