Skip to Content

Dry cooler BC/BD-2x280AB1-B01 C

Dry cooler BC/BD-2x280AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280AB1-B01 C

Heat rejection i
183.49 kW
Air flow
70,434 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 70,434 m³/h
External surface 494.2 m²
Inner volume 76.1 dm³
Fin materialAluminium
Net weight 623 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x280AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
183.489 kW Fluid flow 31.85 m³/h Pressure drop 45.2 kPa
Heat rejection · Low speed (Y)
148.195 kW Fluid flow 25.72 m³/h Pressure drop 30.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.05 not rated not rated not rated not rated not rated
40 183.49 103.92 not rated not rated not rated not rated
45 262.26 183.97 104.68 not rated not rated not rated
50 340.50 262.41 184.43 105.39 not rated not rated
55 418.49 340.36 262.62 184.92 106.07 not rated
60 496.34 418.06 340.33 262.93 185.48 106.81

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 83.95 not rated not rated not rated not rated not rated
40 148.20 84.60 not rated not rated not rated not rated
45 210.89 148.48 85.18 not rated not rated not rated
50 273.09 210.88 148.77 85.72 not rated not rated
55 335.05 272.80 210.92 149.10 86.26 not rated
60 396.88 334.49 272.62 211.08 149.51 86.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 183.489 31.85 45.2
Low speed (Y) 148.195 25.72 30.9

Dimensions

Dimension drawing of BC/BD-2x280AB1-B01 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 2500 mm
H 1200 mm
I 2310 mm
K 3050 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2750 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.