Skip to Content

Dry cooler BC/BD-2x280AD5-B03 C

Dry cooler BC/BD-2x280AD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280AD5-B03 C

Heat rejection i
127.75 kW
Air flow
31,477 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 31,477 m³/h
External surface 696.4 m²
Inner volume 103.7 dm³
Fin materialAluminium
Net weight 680 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x280AD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
127.749 kW Fluid flow 22.16 m³/h Pressure drop 63.3 kPa
Heat rejection · Low speed (Y)
96.087 kW Fluid flow 16.66 m³/h Pressure drop 38.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.51 not rated not rated not rated not rated not rated
40 127.75 77.56 not rated not rated not rated not rated
45 176.61 127.52 77.66 not rated not rated not rated
50 225.00 176.11 127.38 77.81 not rated not rated
55 273.19 224.25 175.77 127.36 78.02 not rated
60 321.25 272.19 223.71 175.61 127.51 78.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.93 not rated not rated not rated not rated not rated
40 96.09 59.05 not rated not rated not rated not rated
45 132.13 96.01 59.18 not rated not rated not rated
50 167.80 131.89 96.00 59.36 not rated not rated
55 203.30 167.41 131.77 96.11 59.60 not rated
60 238.72 202.78 167.20 131.82 96.35 59.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 127.749 22.16 63.3
Low speed (Y) 96.087 16.66 38.2

Dimensions

Dimension drawing of BC/BD-2x280AD5-B03 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 2500 mm
H 1200 mm
I 2310 mm
K 3050 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.