Skip to Content

Dry cooler BC/BD-2x280CB5-B03 C

Dry cooler BC/BD-2x280CB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280CB5-B03 C

Heat rejection i
133.22 kW
Air flow
40,242 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 40,242 m³/h
External surface 609.4 m²
Inner volume 93.1 dm³
Fin materialAluminium
Net weight 715 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x280CB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
133.217 kW Fluid flow 23.12 m³/h Pressure drop 37.8 kPa
Heat rejection · Low speed (Y)
106.366 kW Fluid flow 18.46 m³/h Pressure drop 25.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.96 not rated not rated not rated not rated not rated
40 133.22 78.15 not rated not rated not rated not rated
45 187.10 133.01 78.32 not rated not rated not rated
50 240.52 186.53 132.84 78.48 not rated not rated
55 293.74 239.62 186.07 132.73 78.67 not rated
60 346.84 292.51 238.87 185.72 132.73 78.91

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 62.74 not rated not rated not rated not rated not rated
40 106.37 62.93 not rated not rated not rated not rated
45 148.77 106.25 63.11 not rated not rated not rated
50 190.79 148.40 106.18 63.29 not rated not rated
55 232.63 190.18 148.12 106.16 63.49 not rated
60 274.37 231.79 189.70 147.95 106.24 63.74

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 133.217 23.12 37.8
Low speed (Y) 106.366 18.46 25.3

Dimensions

Dimension drawing of BC/BD-2x280CB5-B03 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2310 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4150 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.