BC/BD-2X563BD5-B01 C
280.36 kW
Defrost: None
Product code: BC/BD-2x280CD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 72,489 m³/h |
|---|---|
| External surface | 1,201.2 m² |
| Inner volume | 166.6 dm³ |
| Fin material | Aluminium |
| Net weight | 886 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 86.9 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x280CD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 166.82 | not rated | not rated | not rated | not rated | not rated |
| 40 | 280.35 | 167.18 | not rated | not rated | not rated | not rated |
| 45 | 390.64 | 279.89 | 167.53 | not rated | not rated | not rated |
| 50 | 499.80 | 389.43 | 279.55 | 167.92 | not rated | not rated |
| 55 | 608.45 | 497.91 | 388.50 | 279.43 | 168.37 | not rated |
| 60 | 716.81 | 605.89 | 496.42 | 387.95 | 279.61 | 169.05 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 129.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 214.89 | 129.47 | not rated | not rated | not rated | not rated |
| 45 | 297.69 | 214.28 | 129.61 | not rated | not rated | not rated |
| 50 | 379.58 | 296.45 | 213.82 | 129.81 | not rated | not rated |
| 55 | 461.03 | 377.73 | 295.45 | 213.54 | 130.13 | not rated |
| 60 | 542.25 | 458.60 | 376.23 | 294.77 | 213.56 | 130.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 280.353 | 48.62 | 51.9 |
| Low speed (Y) | 214.888 | 37.27 | 32.4 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 4150 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4150 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.