Product code: BC/BD-2x280HB5-B03 C

Heat rejection i
94.88 kW
Air flow
34,359 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 34,359 m³/h
External surface 272.3 m²
Inner volume 41.3 dm³
Fin materialAluminium
Net weight 544 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x280HB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
94.878 kW Fluid flow 16.47 m³/h Pressure drop 105.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
75.596 kW Fluid flow 13.12 m³/h Pressure drop 70.3 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 55.33 not rated not rated not rated not rated not rated
40 94.88 55.55 not rated not rated not rated not rated
45 133.62 94.96 55.75 not rated not rated not rated
50 172.10 133.58 95.06 55.96 not rated not rated
55 210.46 171.95 133.60 95.20 56.18 not rated
60 248.77 210.21 171.88 133.68 95.40 56.44

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 44.36 not rated not rated not rated not rated not rated
40 75.60 44.52 not rated not rated not rated not rated
45 106.13 75.63 44.68 not rated not rated not rated
50 136.44 106.06 75.69 44.84 not rated not rated
55 166.65 136.27 106.04 75.79 45.01 not rated
60 196.80 166.38 136.17 106.08 75.94 45.22

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 94.878 16.47 105.2
Low speed (Y) 75.596 13.12 70.3

Dimensions

Dimension drawing of BC/BD-2x280HB5-B03 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.