Skip to Content

Dry cooler BC/BD-2x280HC1-B03 C

Dry cooler BC/BD-2x280HC1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280HC1-B03 C

Heat rejection i
111.39 kW
Air flow
30,668 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 30,668 m³/h
External surface 428.7 m²
Inner volume 51.6 dm³
Fin materialAluminium
Net weight 580 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-2x280HC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
111.393 kW Fluid flow 19.33 m³/h Pressure drop 90.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
84.222 kW Fluid flow 14.61 m³/h Pressure drop 54.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 66.36 not rated not rated not rated not rated not rated
40 111.39 66.56 not rated not rated not rated not rated
45 155.25 111.38 66.76 not rated not rated not rated
50 198.73 155.05 111.40 66.99 not rated not rated
55 242.04 198.36 154.94 111.52 67.26 not rated
60 285.25 241.50 198.13 154.98 111.76 67.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 50.65 not rated not rated not rated not rated not rated
40 84.22 50.85 not rated not rated not rated not rated
45 116.85 84.29 51.06 not rated not rated not rated
50 149.17 116.81 84.40 51.30 not rated not rated
55 181.34 149.03 116.86 84.60 51.56 not rated
60 213.43 181.11 149.02 117.03 84.90 51.91

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 111.393 19.33 90.1
Low speed (Y) 84.222 14.61 54.7

Dimensions

Dimension drawing of BC/BD-2x280HC1-B03 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.