Skip to Content

Dry cooler BC/BD-2x280KB1-B01 C

Dry cooler BC/BD-2x280KB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280KB1-B01 C

Heat rejection i
218.00 kW
Air flow
80,155 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 80,155 m³/h
External surface 535.8 m²
Inner volume 75.9 dm³
Fin materialAluminium
Net weight 688 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x280KB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
218.002 kW Fluid flow 37.83 m³/h Pressure drop 103.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
173.573 kW Fluid flow 30.12 m³/h Pressure drop 69.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 125.90 not rated not rated not rated not rated not rated
40 218.00 126.38 not rated not rated not rated not rated
45 308.24 218.03 126.81 not rated not rated not rated
50 397.88 307.85 218.07 127.21 not rated not rated
55 487.23 397.08 307.54 218.16 127.60 not rated
60 576.44 486.04 396.44 307.36 218.35 128.06

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 100.93 not rated not rated not rated not rated not rated
40 173.57 101.30 not rated not rated not rated not rated
45 244.56 173.52 101.62 not rated not rated not rated
50 315.02 244.15 173.51 101.93 not rated not rated
55 385.22 314.26 243.84 173.57 102.27 not rated
60 455.30 384.14 313.67 243.67 173.74 102.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 218.002 37.83 103.7
Low speed (Y) 173.573 30.12 69.2

Dimensions

Dimension drawing of BC/BD-2x280KB1-B01 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.