Skip to Content

Dry cooler BC/BD-2x280MB1-B03 C

Dry cooler BC/BD-2x280MB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280MB1-B03 C

Heat rejection i
151.66 kW
Air flow
42,326 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 42,326 m³/h
External surface 734.8 m²
Inner volume 88.6 dm³
Fin materialAluminium
Net weight 801 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x280MB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
151.662 kW Fluid flow 26.32 m³/h Pressure drop 75.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
121.352 kW Fluid flow 21.04 m³/h Pressure drop 51.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 90.62 not rated not rated not rated not rated not rated
40 151.66 90.58 not rated not rated not rated not rated
45 211.17 151.15 90.54 not rated not rated not rated
50 270.20 210.23 150.71 90.53 not rated not rated
55 329.00 268.85 209.42 150.35 90.58 not rated
60 387.68 327.24 267.68 208.79 150.17 90.71

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 73.00 not rated not rated not rated not rated not rated
40 121.35 72.93 not rated not rated not rated not rated
45 168.43 120.88 72.79 not rated not rated not rated
50 215.07 167.58 120.32 72.68 not rated not rated
55 261.53 213.87 166.65 119.86 72.61 not rated
60 307.88 259.98 212.59 165.88 119.53 72.59

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 151.662 26.32 75.9
Low speed (Y) 121.352 21.04 51.0

Dimensions

Dimension drawing of BC/BD-2x280MB1-B03 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.