Skip to Content

Dry cooler BC/BD-2x280MD1-B01 C

Dry cooler BC/BD-2x280MD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280MD1-B01 C

Heat rejection i
313.00 kW
Air flow
80,421 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 80,421 m³/h
External surface 1,224.7 m²
Inner volume 159.0 dm³
Fin materialAluminium
Net weight 950 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x280MD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
313.000 kW Fluid flow 54.28 m³/h Pressure drop 104.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
238.972 kW Fluid flow 41.44 m³/h Pressure drop 64.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 188.80 not rated not rated not rated not rated not rated
40 313.00 188.64 not rated not rated not rated not rated
45 433.95 311.86 188.50 not rated not rated not rated
50 553.79 431.89 310.86 188.43 not rated not rated
55 673.13 550.86 430.11 310.08 188.45 not rated
60 792.19 669.35 548.33 428.70 309.65 188.74

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 145.48 not rated not rated not rated not rated not rated
40 238.97 145.31 not rated not rated not rated not rated
45 329.77 237.99 145.17 not rated not rated not rated
50 419.69 328.06 237.16 145.12 not rated not rated
55 509.20 417.29 326.64 236.57 145.19 not rated
60 598.49 506.13 415.29 325.57 236.29 145.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 313.000 54.28 104.3
Low speed (Y) 238.972 41.44 64.7

Dimensions

Dimension drawing of BC/BD-2x280MD1-B01 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.