Skip to Content

Dry cooler BC/BD-2x280MD5-B01 C

Dry cooler BC/BD-2x280MD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x280MD5-B01 C

Heat rejection i
294.99 kW
Air flow
81,533 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 81,533 m³/h
External surface 1,037.5 m²
Inner volume 159.0 dm³
Fin materialAluminium
Net weight 925 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x280MD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
294.985 kW Fluid flow 51.20 m³/h Pressure drop 94.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
228.116 kW Fluid flow 39.56 m³/h Pressure drop 59.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 176.38 not rated not rated not rated not rated not rated
40 294.99 176.32 not rated not rated not rated not rated
45 410.60 294.03 176.27 not rated not rated not rated
50 525.29 408.84 293.19 176.29 not rated not rated
55 639.53 522.75 407.36 292.61 176.41 not rated
60 753.52 636.22 520.59 406.21 292.30 176.71

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 137.58 not rated not rated not rated not rated not rated
40 228.12 137.51 not rated not rated not rated not rated
45 316.23 227.32 137.47 not rated not rated not rated
50 403.54 314.80 226.67 137.48 not rated not rated
55 490.48 401.49 313.60 226.20 137.56 not rated
60 577.21 487.82 399.77 312.71 225.99 137.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 294.985 51.20 94.0
Low speed (Y) 228.116 39.56 59.6

Dimensions

Dimension drawing of BC/BD-2x280MD5-B01 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 2260 mm
K 5450 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.