BC/BD-2X563CB1-B01 C
258.72 kW
Defrost: None
Product code: BC/BD-2x291BB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 102,872 m³/h |
|---|---|
| External surface | 720.7 m² |
| Inner volume | 117.0 dm³ |
| Fin material | Aluminium |
| Net weight | 773 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 96.6 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x291BB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 140.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 258.77 | 142.58 | not rated | not rated | not rated | not rated |
| 45 | 374.02 | 259.77 | 144.13 | not rated | not rated | not rated |
| 50 | 488.40 | 374.39 | 260.68 | 145.51 | not rated | not rated |
| 55 | 602.41 | 488.20 | 374.76 | 261.55 | 146.78 | not rated |
| 60 | 716.17 | 601.64 | 488.10 | 375.23 | 262.47 | 148.03 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 114.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 209.33 | 116.30 | not rated | not rated | not rated | not rated |
| 45 | 301.18 | 210.11 | 117.60 | not rated | not rated | not rated |
| 50 | 392.17 | 301.43 | 210.84 | 118.76 | not rated | not rated |
| 55 | 482.79 | 391.96 | 301.71 | 211.56 | 119.84 | not rated |
| 60 | 573.18 | 482.12 | 391.86 | 302.11 | 212.35 | 120.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 258.768 | 44.91 | 18.7 |
| Low speed (Y) | 209.329 | 36.33 | 12.7 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 4150 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4150 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.