BC/BD-t-680GC5-B01 C
292.92 kW
Defrost: None
Product code: BC/BD-2x291ED1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 84,520 m³/h |
|---|---|
| External surface | 961.0 m² |
| Inner volume | 141.8 dm³ |
| Fin material | Aluminium |
| Net weight | 800 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x291ED1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 169.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 292.92 | 170.96 | not rated | not rated | not rated | not rated |
| 45 | 412.56 | 293.24 | 171.84 | not rated | not rated | not rated |
| 50 | 531.06 | 412.28 | 293.58 | 172.72 | not rated | not rated |
| 55 | 649.05 | 530.28 | 412.15 | 294.08 | 173.65 | not rated |
| 60 | 766.77 | 647.79 | 529.72 | 412.33 | 294.83 | 174.72 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 292.921 | 50.84 | 46.6 |
| A | 3150 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2900 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 3450 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3450 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.