BC/BD-2x680AC5-B03 C
364.04 kW
Defrost: None
Product code: BC/BD-2x291GD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 104,984 m³/h |
|---|---|
| External surface | 1,392.9 m² |
| Inner volume | 235.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,070 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.4 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x291GD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 209.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 364.26 | 210.59 | not rated | not rated | not rated | not rated |
| 45 | 514.39 | 364.09 | 211.63 | not rated | not rated | not rated |
| 50 | 662.91 | 513.04 | 363.98 | 212.58 | not rated | not rated |
| 55 | 810.76 | 660.56 | 511.97 | 364.02 | 213.55 | not rated |
| 60 | 958.18 | 807.39 | 658.60 | 511.26 | 364.28 | 214.61 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 165.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 284.91 | 166.38 | not rated | not rated | not rated | not rated |
| 45 | 400.20 | 284.73 | 167.23 | not rated | not rated | not rated |
| 50 | 514.08 | 399.11 | 284.61 | 168.02 | not rated | not rated |
| 55 | 627.31 | 512.16 | 398.24 | 284.67 | 168.84 | not rated |
| 60 | 740.18 | 624.61 | 510.61 | 397.71 | 284.97 | 169.76 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 364.259 | 63.22 | 18.0 |
| Low speed (Y) | 284.912 | 49.41 | 11.6 |
| A | 5350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 2310 mm |
| K | 5850 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 5850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.