Skip to Content

Dry cooler BC/BD-2x291KB5-B04 C

Dry cooler BC/BD-2x291KB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291KB5-B04 C

Heat rejection i
201.77 kW
Air flow
98,476 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 98,476 m³/h
External surface 363.1 m²
Inner volume 65.6 dm³
Fin materialAluminium
Net weight 631 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x291KB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
201.773 kW Fluid flow 35.02 m³/h Pressure drop 74.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
163.132 kW Fluid flow 28.32 m³/h Pressure drop 51.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 113.68 not rated not rated not rated not rated not rated
40 201.77 114.53 not rated not rated not rated not rated
45 288.32 202.33 115.28 not rated not rated not rated
50 374.40 288.63 202.85 115.98 not rated not rated
55 460.25 374.49 288.97 203.39 116.64 not rated
60 545.99 460.13 374.65 289.38 203.98 117.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 92.43 not rated not rated not rated not rated not rated
40 163.13 93.15 not rated not rated not rated not rated
45 232.41 163.58 93.78 not rated not rated not rated
50 301.25 232.66 164.02 94.37 not rated not rated
55 369.90 301.31 232.95 164.48 94.94 not rated
60 438.43 369.79 301.47 233.32 165.00 95.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 201.773 35.02 74.7
Low speed (Y) 163.132 28.32 51.2

Dimensions

Dimension drawing of BC/BD-2x291KB5-B04 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2900 mm
H 1400 mm
I 2260 mm
K 3450 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.