Dry cooler BC/BD-2x291LB5-B04 C

Dry cooler BC/BD-2x291LB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291LB5-B04 C

Heat rejection i
225.62 kW
Air flow
105,034 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 105,034 m³/h
External surface 453.9 m²
Inner volume 75.9 dm³
Fin materialAluminium
Net weight 699 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.4 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2x291LB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
225.623 kW Fluid flow 39.16 m³/h Pressure drop 41.9 kPa
Heat rejection · Low speed (Y)
183.482 kW Fluid flow 31.85 m³/h Pressure drop 28.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 125.71 not rated not rated not rated not rated not rated
40 225.62 126.85 not rated not rated not rated not rated
45 323.53 226.25 127.82 not rated not rated not rated
50 420.84 323.76 226.82 128.70 not rated not rated
55 517.87 420.71 324.01 227.39 129.51 not rated
60 614.75 517.41 420.67 324.34 228.00 130.33

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 102.75 not rated not rated not rated not rated not rated
40 183.48 103.72 not rated not rated not rated not rated
45 262.32 184.00 104.57 not rated not rated not rated
50 340.59 262.52 184.49 105.32 not rated not rated
55 418.61 340.49 262.74 184.99 106.04 not rated
60 496.49 418.25 340.50 263.06 185.54 106.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 225.623 39.16 41.9
Low speed (Y) 183.482 31.85 28.9

Dimensions

Dimension drawing of BC/BD-2x291LB5-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads