Skip to Content

Dry cooler BC/BD-2x380AB1-B01 C

Dry cooler BC/BD-2x380AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380AB1-B01 C

Heat rejection i
277.84 kW
Air flow
105,651 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 105,651 m³/h
External surface 741.3 m²
Inner volume 119.1 dm³
Fin materialAluminium
Net weight 897 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x380AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
277.835 kW Fluid flow 48.22 m³/h Pressure drop 57.4 kPa
Heat rejection · Low speed (Y)
224.293 kW Fluid flow 38.93 m³/h Pressure drop 39.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 157.33 not rated not rated not rated not rated not rated
40 277.84 158.44 not rated not rated not rated not rated
45 395.92 278.42 159.44 not rated not rated not rated
50 513.24 396.04 278.99 160.37 not rated not rated
55 630.19 512.92 396.25 279.63 161.31 not rated
60 746.93 629.45 512.79 396.65 280.40 162.30

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 128.09 not rated not rated not rated not rated not rated
40 224.29 128.93 not rated not rated not rated not rated
45 318.26 224.61 129.67 not rated not rated not rated
50 411.51 318.14 224.95 130.38 not rated not rated
55 504.41 410.98 318.13 225.36 131.10 not rated
60 597.14 503.49 410.65 318.31 225.92 131.89

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 277.835 48.22 57.4
Low speed (Y) 224.293 38.93 39.2

Dimensions

Dimension drawing of BC/BD-2x380AB1-B01 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 3700 mm
H 1200 mm
I 2310 mm
K 4250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3950 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.