BC/BD-2X463CB5-B01 C
196.92 kW
Defrost: None
Product code: BC/BD-2x380AD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 45,622 m³/h |
|---|---|
| External surface | 1,234.9 m² |
| Inner volume | 150.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,014 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2x380AD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 121.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 196.95 | 121.19 | not rated | not rated | not rated | not rated |
| 45 | 270.58 | 196.55 | 121.23 | not rated | not rated | not rated |
| 50 | 343.49 | 269.78 | 196.21 | 121.37 | not rated | not rated |
| 55 | 416.07 | 342.32 | 269.10 | 196.09 | 121.65 | not rated |
| 60 | 488.47 | 414.54 | 341.33 | 268.77 | 196.26 | 122.13 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 144.88 | 90.29 | not rated | not rated | not rated | not rated |
| 45 | 197.92 | 144.71 | 90.41 | not rated | not rated | not rated |
| 50 | 250.43 | 197.52 | 144.62 | 90.63 | not rated | not rated |
| 55 | 302.70 | 249.82 | 197.26 | 144.72 | 90.98 | not rated |
| 60 | 354.83 | 301.89 | 249.41 | 197.29 | 145.07 | 91.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 196.947 | 34.15 | 89.6 |
| Low speed (Y) | 144.881 | 25.13 | 52.0 |
| A | 3950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 4250 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4250 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.