BC/BD-t-2X450AC1-B09 C
200.99 kW
Defrost: None
Product code: BC/BD-2x380CB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 60,364 m³/h |
|---|---|
| External surface | 914.1 m² |
| Inner volume | 136.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,038 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2x380CB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 118.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 201.00 | 118.45 | not rated | not rated | not rated | not rated |
| 45 | 281.76 | 200.62 | 118.61 | not rated | not rated | not rated |
| 50 | 361.85 | 280.85 | 200.30 | 118.79 | not rated | not rated |
| 55 | 441.65 | 360.46 | 280.10 | 200.09 | 119.01 | not rated |
| 60 | 521.25 | 439.75 | 359.29 | 279.54 | 200.05 | 119.33 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 160.43 | 95.36 | not rated | not rated | not rated | not rated |
| 45 | 223.98 | 160.21 | 95.55 | not rated | not rated | not rated |
| 50 | 286.98 | 223.38 | 160.03 | 95.76 | not rated | not rated |
| 55 | 349.71 | 286.02 | 222.92 | 159.98 | 96.02 | not rated |
| 60 | 412.29 | 348.41 | 285.26 | 222.64 | 160.07 | 96.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 201.000 | 34.88 | 50.4 |
| Low speed (Y) | 160.434 | 27.84 | 33.7 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5900 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.