Skip to Content

Dry cooler BC/BD-2x380CD5-B01 C

Dry cooler BC/BD-2x380CD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380CD5-B01 C

Heat rejection i
402.02 kW
Air flow
111,412 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 111,412 m³/h
External surface 1,523.3 m²
Inner volume 228.0 dm³
Fin materialAluminium
Net weight 1,244 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.5 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x380CD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
402.017 kW Fluid flow 69.78 m³/h Pressure drop 68.9 kPa
Heat rejection · Low speed (Y)
311.377 kW Fluid flow 54.00 m³/h Pressure drop 43.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 238.22 not rated not rated not rated not rated not rated
40 402.02 238.71 not rated not rated not rated not rated
45 561.52 401.44 239.17 not rated not rated not rated
50 719.69 560.02 400.99 239.68 not rated not rated
55 877.19 717.28 558.86 400.87 240.34 not rated
60 1034.34 873.92 715.39 558.17 401.14 241.21

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 186.51 not rated not rated not rated not rated not rated
40 311.38 186.74 not rated not rated not rated not rated
45 432.72 310.66 186.96 not rated not rated not rated
50 552.87 431.17 310.10 187.25 not rated not rated
55 672.47 550.53 429.93 309.80 187.61 not rated
60 791.76 669.36 548.65 429.12 309.84 188.25

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 402.017 69.78 68.9
Low speed (Y) 311.377 54.00 43.6

Dimensions

Dimension drawing of BC/BD-2x380CD5-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 2310 mm
K 5900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5900 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.