BC/BD-2X450CD5-B09 C
158.17 kW
Defrost: None
Product code: BC/BD-2x380HC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,556 m³/h |
|---|---|
| External surface | 544.7 m² |
| Inner volume | 79.8 dm³ |
| Fin material | Aluminium |
| Net weight | 822 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x380HC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 93.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 158.13 | 93.74 | not rated | not rated | not rated | not rated |
| 45 | 221.31 | 158.20 | 94.06 | not rated | not rated | not rated |
| 50 | 283.99 | 221.14 | 158.32 | 94.41 | not rated | not rated |
| 55 | 346.43 | 283.60 | 221.10 | 158.54 | 94.80 | not rated |
| 60 | 408.74 | 345.83 | 283.40 | 221.22 | 158.90 | 95.29 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 72.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 122.02 | 72.98 | not rated | not rated | not rated | not rated |
| 45 | 170.06 | 122.17 | 73.31 | not rated | not rated | not rated |
| 50 | 217.70 | 170.08 | 122.37 | 73.67 | not rated | not rated |
| 55 | 265.13 | 217.60 | 170.22 | 122.68 | 74.07 | not rated |
| 60 | 312.47 | 264.92 | 217.66 | 170.50 | 123.12 | 74.55 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 158.129 | 27.44 | 74.5 |
| Low speed (Y) | 122.016 | 21.18 | 47.0 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3800 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.