Skip to Content

Dry cooler BC/BD-2x380HC5-B03 C

Dry cooler BC/BD-2x380HC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380HC5-B03 C

Heat rejection i
158.13 kW
Air flow
47,556 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 47,556 m³/h
External surface 544.7 m²
Inner volume 79.8 dm³
Fin materialAluminium
Net weight 822 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x380HC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
158.129 kW Fluid flow 27.44 m³/h Pressure drop 74.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
122.016 kW Fluid flow 21.18 m³/h Pressure drop 47.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 93.39 not rated not rated not rated not rated not rated
40 158.13 93.74 not rated not rated not rated not rated
45 221.31 158.20 94.06 not rated not rated not rated
50 283.99 221.14 158.32 94.41 not rated not rated
55 346.43 283.60 221.10 158.54 94.80 not rated
60 408.74 345.83 283.40 221.22 158.90 95.29

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 72.64 not rated not rated not rated not rated not rated
40 122.02 72.98 not rated not rated not rated not rated
45 170.06 122.17 73.31 not rated not rated not rated
50 217.70 170.08 122.37 73.67 not rated not rated
55 265.13 217.60 170.22 122.68 74.07 not rated
60 312.47 264.92 217.66 170.50 123.12 74.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 158.129 27.44 74.5
Low speed (Y) 122.016 21.18 47.0

Dimensions

Dimension drawing of BC/BD-2x380HC5-B03 C
Dimension drawing
Dimensions as drawn
A 3500 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3250 mm
H 1050 mm
I 2260 mm
K 3800 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3800 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.