Skip to Content

Dry cooler BC/BD-2x380ND1-B01 C

Dry cooler BC/BD-2x380ND1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x380ND1-B01 C

Heat rejection i
486.80 kW
Air flow
120,165 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 120,165 m³/h
External surface 2,471.0 m²
Inner volume 320.2 dm³
Fin materialAluminium
Net weight 1,587 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x380ND1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
486.798 kW Fluid flow 84.42 m³/h Pressure drop 42.1 kPa
Heat rejection · Low speed (Y)
370.579 kW Fluid flow 64.28 m³/h Pressure drop 25.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 292.10 not rated not rated not rated not rated not rated
40 486.80 292.09 not rated not rated not rated not rated
45 675.55 485.05 292.18 not rated not rated not rated
50 862.28 672.19 483.57 292.34 not rated not rated
55 1048.08 857.40 669.36 482.49 292.64 not rated
60 1233.36 1041.72 853.28 667.20 481.89 293.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 224.85 not rated not rated not rated not rated not rated
40 370.58 224.82 not rated not rated not rated not rated
45 511.32 369.04 224.78 not rated not rated not rated
50 650.44 508.51 367.75 224.84 not rated not rated
55 788.81 646.44 506.16 366.83 225.09 not rated
60 926.77 783.65 643.08 504.40 366.39 225.65

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 486.798 84.42 42.1
Low speed (Y) 370.579 64.28 25.9

Dimensions

Dimension drawing of BC/BD-2x380ND1-B01 C
Dimension drawing
Dimensions as drawn
A 7750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 8250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.