Skip to Content

Dry cooler BC/BD-2x391HC1-B04 C

Dry cooler BC/BD-2x391HC1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x391HC1-B04 C

Heat rejection i
571.69 kW
Air flow
154,807 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 154,807 m³/h
External surface 1,875.7 m²
Inner volume 382.2 dm³
Fin materialAluminium
Net weight 1,526 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x391HC1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
571.690 kW Fluid flow 99.22 m³/h Pressure drop 84.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
440.782 kW Fluid flow 76.45 m³/h Pressure drop 53.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 340.41 not rated not rated not rated not rated not rated
40 571.69 340.60 not rated not rated not rated not rated
45 796.99 570.12 340.81 not rated not rated not rated
50 1020.38 793.96 568.91 341.10 not rated not rated
55 1242.84 1015.87 791.45 568.13 341.63 not rated
60 1464.80 1236.88 1012.11 789.67 567.91 342.49

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 265.26 not rated not rated not rated not rated not rated
40 440.78 265.39 not rated not rated not rated not rated
45 611.45 439.58 265.50 not rated not rated not rated
50 780.47 609.07 438.64 265.71 not rated not rated
55 948.74 776.97 607.16 438.08 266.21 not rated
60 1116.57 944.13 774.13 605.87 438.04 266.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 571.690 99.22 84.7
Low speed (Y) 440.782 76.45 53.3

Dimensions

Dimension drawing of BC/BD-2x391HC1-B04 C
Dimension drawing
Dimensions as drawn
A 7750 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 2310 mm
K 8250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.