Skip to Content

Dry cooler BC/BD-2x480CD1-B01 C

Dry cooler BC/BD-2x480CD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480CD1-B01 C

Heat rejection i
560.41 kW
Air flow
144,977 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 144,977 m³/h
External surface 2,402.4 m²
Inner volume 313.1 dm³
Fin materialAluminium
Net weight 1,693 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.9 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480CD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
560.413 kW Fluid flow 97.19 m³/h Pressure drop 52.9 kPa
Heat rejection · Low speed (Y)
429.574 kW Fluid flow 74.49 m³/h Pressure drop 32.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 333.32 not rated not rated not rated not rated not rated
40 560.41 334.05 not rated not rated not rated not rated
45 781.00 559.49 334.76 not rated not rated not rated
50 999.34 778.60 558.83 335.56 not rated not rated
55 1216.65 995.57 776.75 558.60 336.50 not rated
60 1433.38 1211.54 992.60 775.65 558.98 337.84

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 258.41 not rated not rated not rated not rated not rated
40 429.57 258.71 not rated not rated not rated not rated
45 595.20 428.37 259.02 not rated not rated not rated
50 758.98 592.72 427.45 259.43 not rated not rated
55 921.90 755.29 590.73 426.91 260.07 not rated
60 1084.34 917.05 752.31 589.38 426.96 261.02

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 560.413 97.19 52.9
Low speed (Y) 429.574 74.49 32.9

Dimensions

Dimension drawing of BC/BD-2x480CD1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.