Skip to Content

Dry cooler BC/BD-2x480FC1-B01 C

Dry cooler BC/BD-2x480FC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480FC1-B01 C

Heat rejection i
539.10 kW
Air flow
144,878 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 144,878 m³/h
External surface 1,823.6 m²
Inner volume 373.4 dm³
Fin materialAluminium
Net weight 1,599 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.9 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480FC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
539.102 kW Fluid flow 93.50 m³/h Pressure drop 74.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
414.632 kW Fluid flow 71.91 m³/h Pressure drop 46.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 321.07 not rated not rated not rated not rated not rated
40 539.10 321.58 not rated not rated not rated not rated
45 751.53 538.24 322.12 not rated not rated not rated
50 962.06 749.43 537.65 322.74 not rated not rated
55 1171.71 958.77 747.83 537.46 323.60 not rated
60 1380.86 1167.26 956.23 746.93 537.85 324.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 249.57 not rated not rated not rated not rated not rated
40 414.63 249.73 not rated not rated not rated not rated
45 575.05 413.53 249.83 not rated not rated not rated
50 733.89 572.84 412.69 250.12 not rated not rated
55 892.01 730.63 571.08 412.20 250.65 not rated
60 1049.71 887.72 728.01 569.92 412.27 251.49

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 539.102 93.50 74.4
Low speed (Y) 414.632 71.91 46.6

Dimensions

Dimension drawing of BC/BD-2x480FC1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 8050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.