BC/BD-2x380KD1-B03 C
228.09 kW
Defrost: None
Product code: BC/BD-2x480HD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 56,498 m³/h |
|---|---|
| External surface | 1,071.6 m² |
| Inner volume | 127.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,148 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 2,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2x480HD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 137.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 228.02 | 138.13 | not rated | not rated | not rated | not rated |
| 45 | 315.67 | 227.98 | 138.58 | not rated | not rated | not rated |
| 50 | 402.45 | 315.26 | 228.09 | 139.10 | not rated | not rated |
| 55 | 488.83 | 401.69 | 315.11 | 228.42 | 139.74 | not rated |
| 60 | 574.98 | 487.75 | 401.31 | 315.32 | 229.05 | 140.57 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | not rated | not rated | not rated | not rated |
| 50 | not rated | not rated | not rated | not rated | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | 103.84 | not rated |
| 60 | not rated | not rated | not rated | not rated | 168.40 | 104.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 228.018 | 39.55 | 59.2 |
| Low speed (Y) | — | — | — |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 4850 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.