Skip to Content

Dry cooler BC/BD-2x480ND1-B01 C

Dry cooler BC/BD-2x480ND1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480ND1-B01 C

Heat rejection i
656.91 kW
Air flow
160,220 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 160,220 m³/h
External surface 3,294.7 m²
Inner volume 405.3 dm³
Fin materialAluminium
Net weight 2,089 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480ND1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
656.909 kW Fluid flow 113.93 m³/h Pressure drop 92.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
499.425 kW Fluid flow 86.63 m³/h Pressure drop 56.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 398.65 not rated not rated not rated not rated not rated
40 656.91 398.08 not rated not rated not rated not rated
45 907.89 654.07 397.61 not rated not rated not rated
50 1156.44 902.99 651.68 397.34 not rated not rated
55 1403.87 1149.56 898.86 649.89 397.37 not rated
60 1650.67 1395.05 1143.75 895.67 648.78 397.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 306.54 not rated not rated not rated not rated not rated
40 499.43 305.94 not rated not rated not rated not rated
45 686.45 497.00 305.44 not rated not rated not rated
50 871.56 682.40 494.97 305.15 not rated not rated
55 1055.79 865.97 679.01 493.48 305.18 not rated
60 1239.54 1048.69 861.28 676.46 492.68 305.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 656.909 113.93 92.0
Low speed (Y) 499.425 86.63 56.5

Dimensions

Dimension drawing of BC/BD-2x480ND1-B01 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10650 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.