Skip to Content

Dry cooler BC/BD-2x480OC5-B03 C

Dry cooler BC/BD-2x480OC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480OC5-B03 C

Heat rejection i
342.44 kW
Air flow
80,680 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 80,680 m³/h
External surface 2,119.7 m²
Inner volume 469.5 dm³
Fin materialAluminium
Net weight 1,875 kg
Fans
Quantity 8
Diameter 800 mm
Speed 435 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 73.0 dB(A)
Energy class B
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x480OC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
342.436 kW Fluid flow 59.38 m³/h Pressure drop 97.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
264.021 kW Fluid flow 45.78 m³/h Pressure drop 61.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.40 not rated not rated not rated not rated not rated
40 342.44 210.61 not rated not rated not rated not rated
45 470.08 340.48 209.93 not rated not rated not rated
50 596.62 467.04 338.81 209.43 not rated not rated
55 722.65 592.52 464.44 337.51 209.15 not rated
60 848.40 717.51 589.02 462.40 336.67 209.18

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.43 not rated not rated not rated not rated not rated
40 264.02 163.92 not rated not rated not rated not rated
45 360.95 262.70 163.51 not rated not rated not rated
50 457.02 358.88 261.62 163.24 not rated not rated
55 552.69 454.23 357.18 260.83 163.17 not rated
60 648.16 549.20 451.93 355.91 260.42 163.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 342.436 59.38 97.0
Low speed (Y) 264.021 45.78 61.1

Dimensions

Dimension drawing of BC/BD-2x480OC5-B03 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.