Skip to Content

Dry cooler BC/BD-2x480OD5-B01 C

Dry cooler BC/BD-2x480OD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480OD5-B01 C

Heat rejection i
627.35 kW
Air flow
157,351 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 157,351 m³/h
External surface 2,649.6 m²
Inner volume 598.5 dm³
Fin materialAluminium
Net weight 2,091 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x480OD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
627.345 kW Fluid flow 108.81 m³/h Pressure drop 35.3 kPa
Heat rejection · Low speed (Y)
476.552 kW Fluid flow 82.64 m³/h Pressure drop 21.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 376.39 not rated not rated not rated not rated not rated
40 627.35 376.53 not rated not rated not rated not rated
45 870.96 625.28 376.57 not rated not rated not rated
50 1112.10 866.95 623.56 376.83 not rated not rated
55 1352.09 1106.25 863.60 622.36 377.36 not rated
60 1591.43 1344.44 1101.35 861.13 621.88 378.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 288.99 not rated not rated not rated not rated not rated
40 476.55 288.95 not rated not rated not rated not rated
45 658.12 474.73 288.95 not rated not rated not rated
50 837.69 654.74 473.24 289.08 not rated not rated
55 1016.33 832.86 651.97 472.21 289.46 not rated
60 1194.47 1010.09 828.88 649.96 471.80 290.20

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 627.345 108.81 35.3
Low speed (Y) 476.552 82.64 21.5

Dimensions

Dimension drawing of BC/BD-2x480OD5-B01 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10650 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.