Skip to Content

Dry cooler BC/BD-2x491GC5-B04 C

Dry cooler BC/BD-2x491GC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x491GC5-B04 C

Heat rejection i
664.24 kW
Air flow
216,417 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 216,417 m³/h
External surface 2,228.6 m²
Inner volume 337.2 dm³
Fin materialAluminium
Net weight 1,883 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x491GC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
664.241 kW Fluid flow 115.28 m³/h Pressure drop 28.6 kPa
Heat rejection · Low speed (Y)
531.681 kW Fluid flow 92.27 m³/h Pressure drop 19.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 377.20 not rated not rated not rated not rated not rated
40 664.24 379.65 not rated not rated not rated not rated
45 943.72 664.41 381.71 not rated not rated not rated
50 1220.79 942.03 664.60 383.57 not rated not rated
55 1496.74 1217.28 940.56 664.93 385.41 not rated
60 1772.01 1491.51 1214.32 939.58 665.61 387.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 304.50 not rated not rated not rated not rated not rated
40 531.68 306.54 not rated not rated not rated not rated
45 751.89 531.78 308.30 not rated not rated not rated
50 969.89 750.43 531.89 309.88 not rated not rated
55 1186.76 966.90 749.26 532.23 311.45 not rated
60 1403.10 1182.48 964.55 748.51 532.90 313.15

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 664.241 115.28 28.6
Low speed (Y) 531.681 92.27 19.0

Dimensions

Dimension drawing of BC/BD-2x491GC5-B04 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10650 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.