Dry cooler BC/BD-2x491HB5-B04 C

Dry cooler BC/BD-2x491HB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x491HB5-B04 C

Heat rejection i
623.66 kW
Air flow
217,894 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 217,894 m³/h
External surface 1,589.8 m²
Inner volume 385.0 dm³
Fin materialAluminium
Net weight 1,763 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x491HB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
623.657 kW Fluid flow 108.24 m³/h Pressure drop 72.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
502.147 kW Fluid flow 87.16 m³/h Pressure drop 49.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 361.71 not rated not rated not rated not rated not rated
40 623.66 362.61 not rated not rated not rated not rated
45 880.27 623.11 363.43 not rated not rated not rated
50 1135.12 878.33 622.66 364.27 not rated not rated
55 1389.21 1131.88 876.71 622.45 365.14 not rated
60 1642.81 1384.61 1129.11 875.55 622.60 366.20

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 293.44 not rated not rated not rated not rated not rated
40 502.15 294.20 not rated not rated not rated not rated
45 706.13 501.68 294.89 not rated not rated not rated
50 908.58 704.54 501.34 295.58 not rated not rated
55 1110.30 905.92 703.27 501.24 296.40 not rated
60 1311.62 1106.60 903.75 702.48 501.53 297.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 623.657 108.24 72.3
Low speed (Y) 502.147 87.16 49.1

Dimensions

Dimension drawing of BC/BD-2x491HB5-B04 C
Dimension drawing
Dimensions as drawn
A 10150 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10650 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.