BC/BD-791FC1-B04 C
496.90 kW
Defrost: None
Product code: BC/BD-2x491KC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 180,778 m³/h |
|---|---|
| External surface | 1,143.1 m² |
| Inner volume | 173.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,292 kg |
| Quantity | 8 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 22,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 100.7 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x491KC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 274.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 496.92 | 277.73 | not rated | not rated | not rated | not rated |
| 45 | 713.40 | 498.84 | 280.73 | not rated | not rated | not rated |
| 50 | 928.03 | 714.28 | 500.63 | 283.40 | not rated | not rated |
| 55 | 1141.81 | 927.93 | 715.23 | 502.48 | 285.92 | not rated |
| 60 | 1355.08 | 1140.84 | 928.14 | 716.45 | 504.47 | 288.44 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 496.923 | 86.24 | 23.8 |
| A | 6150 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5700 mm |
| H | 1400 mm |
| I | 2260 mm |
| K | 6650 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6650 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.