Skip to Content

Dry cooler BC/BD-2x580DC5-B03 C

Dry cooler BC/BD-2x580DC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580DC5-B03 C

Heat rejection i
304.11 kW
Air flow
78,607 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 78,607 m³/h
External surface 1,324.8 m²
Inner volume 309.4 dm³
Fin materialAluminium
Net weight 1,525 kg
Fans
Quantity 10
Diameter 800 mm
Speed 435 rpm
Power 3,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 42.0 dB(A)
Sound power 74.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x580DC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
304.107 kW Fluid flow 52.74 m³/h Pressure drop 51.8 kPa
Heat rejection · Low speed (Y)
229.896 kW Fluid flow 39.87 m³/h Pressure drop 31.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 183.07 not rated not rated not rated not rated not rated
40 304.11 183.38 not rated not rated not rated not rated
45 421.99 303.75 183.72 not rated not rated not rated
50 538.81 421.06 303.60 184.14 not rated not rated
55 655.13 537.33 420.46 303.70 184.69 not rated
60 771.18 653.12 536.31 420.28 304.16 185.50

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 139.79 not rated not rated not rated not rated not rated
40 229.90 140.15 not rated not rated not rated not rated
45 317.42 229.85 140.55 not rated not rated not rated
50 404.10 317.04 229.96 141.04 not rated not rated
55 490.38 403.40 316.92 230.31 141.68 not rated
60 576.45 489.39 403.08 317.18 230.98 142.51

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 304.107 52.74 51.8
Low speed (Y) 229.896 39.87 31.5

Dimensions

Dimension drawing of BC/BD-2x580DC5-B03 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 6650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.