Skip to Content

Dry cooler BC/BD-2x580DD1-B01 C

Dry cooler BC/BD-2x580DD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580DD1-B01 C

Heat rejection i
563.62 kW
Air flow
141,872 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 141,872 m³/h
External surface 1,954.6 m²
Inner volume 398.4 dm³
Fin materialAluminium
Net weight 1,723 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.6 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x580DD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
563.617 kW Fluid flow 97.76 m³/h Pressure drop 100.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
421.712 kW Fluid flow 73.13 m³/h Pressure drop 59.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 340.13 not rated not rated not rated not rated not rated
40 563.62 340.76 not rated not rated not rated not rated
45 781.14 563.12 341.40 not rated not rated not rated
50 996.63 779.64 563.00 342.31 not rated not rated
55 1211.18 994.19 778.79 563.42 343.58 not rated
60 1425.21 1207.83 992.66 778.79 564.55 345.26

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 257.49 not rated not rated not rated not rated not rated
40 421.71 258.17 not rated not rated not rated not rated
45 581.12 421.70 258.73 not rated not rated not rated
50 738.93 580.54 421.62 259.45 not rated not rated
55 896.00 737.82 579.93 422.00 260.47 not rated
60 1052.66 894.39 736.73 580.04 422.99 261.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 563.617 97.76 100.2
Low speed (Y) 421.712 73.13 59.9

Dimensions

Dimension drawing of BC/BD-2x580DD1-B01 C
Dimension drawing
Dimensions as drawn
A 6550 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 2310 mm
K 7050 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7050 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.