Skip to Content

Dry cooler BC/BD-2x580FC5-B03 C

Dry cooler BC/BD-2x580FC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x580FC5-B03 C

Heat rejection i
374.18 kW
Air flow
92,548 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 92,548 m³/h
External surface 1,931.1 m²
Inner volume 428.2 dm³
Fin materialAluminium
Net weight 1,887 kg
Fans
Quantity 10
Diameter 800 mm
Speed 435 rpm
Power 3,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 41.0 dB(A)
Sound power 74.0 dB(A)
Energy class B
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x580FC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
374.176 kW Fluid flow 64.90 m³/h Pressure drop 52.3 kPa
Heat rejection · Low speed (Y)
285.978 kW Fluid flow 49.59 m³/h Pressure drop 32.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 227.30 not rated not rated not rated not rated not rated
40 374.18 227.12 not rated not rated not rated not rated
45 517.11 372.96 227.02 not rated not rated not rated
50 658.73 514.92 371.95 227.03 not rated not rated
55 799.73 655.60 513.09 371.25 227.24 not rated
60 940.41 795.69 652.98 511.75 371.01 227.75

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 175.39 not rated not rated not rated not rated not rated
40 285.98 175.08 not rated not rated not rated not rated
45 393.40 284.68 174.91 not rated not rated not rated
50 499.77 391.23 283.76 174.86 not rated not rated
55 605.66 496.76 389.63 283.14 174.99 not rated
60 711.29 601.84 494.52 388.49 282.90 175.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 374.176 64.90 52.3
Low speed (Y) 285.978 49.59 32.3

Dimensions

Dimension drawing of BC/BD-2x580FC5-B03 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 9400 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.