BC/BD-2x491DC1-B04 C
650.12 kW
Defrost: None
Product code: BC/BD-2x591FC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 217,779 m³/h |
|---|---|
| External surface | 1,545.6 m² |
| Inner volume | 376.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,749 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 102.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2x591FC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 372.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 650.90 | 374.91 | not rated | not rated | not rated | not rated |
| 45 | 923.06 | 652.16 | 377.20 | not rated | not rated | not rated |
| 50 | 1193.15 | 923.23 | 653.48 | 379.35 | not rated | not rated |
| 55 | 1462.24 | 1192.31 | 923.77 | 654.94 | 381.53 | not rated |
| 60 | 1730.82 | 1460.44 | 1192.04 | 924.64 | 656.74 | 383.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 650.904 | 112.97 | 40.2 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1400 mm |
| I | 2310 mm |
| K | 8050 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 8050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.