BC/BD-2X563CD5-B19 C
367.26 kW
Defrost: None
Product code: BC/BD-2x680DC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 94,328 m³/h |
|---|---|
| External surface | 1,589.8 m² |
| Inner volume | 362.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,812 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x680DC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 222.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 367.25 | 222.52 | not rated | not rated | not rated | not rated |
| 45 | 508.55 | 366.70 | 222.78 | not rated | not rated | not rated |
| 50 | 648.63 | 507.33 | 366.39 | 223.18 | not rated | not rated |
| 55 | 788.15 | 646.76 | 506.50 | 366.42 | 223.71 | not rated |
| 60 | 927.36 | 785.65 | 645.46 | 506.21 | 366.89 | 224.61 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 169.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 277.46 | 169.95 | not rated | not rated | not rated | not rated |
| 45 | 382.35 | 277.31 | 170.31 | not rated | not rated | not rated |
| 50 | 486.27 | 381.81 | 277.36 | 170.82 | not rated | not rated |
| 55 | 589.75 | 485.37 | 381.61 | 277.71 | 171.50 | not rated |
| 60 | 692.99 | 588.50 | 484.93 | 381.86 | 278.46 | 172.44 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 367.246 | 63.69 | 84.9 |
| Low speed (Y) | 277.461 | 48.12 | 51.6 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 7850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.