Dry cooler BC/BD-2x680FC5-B03 C

Dry cooler BC/BD-2x680FC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x680FC5-B03 C

Heat rejection i
451.50 kW
Air flow
111,057 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 111,057 m³/h
External surface 2,317.3 m²
Inner volume 527.6 dm³
Fin materialAluminium
Net weight 2,246 kg
Fans
Quantity 12
Diameter 800 mm
Speed 435 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 42.0 dB(A)
Sound power 75.0 dB(A)
Energy class B
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x680FC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
451.500 kW Fluid flow 78.31 m³/h Pressure drop 78.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
344.889 kW Fluid flow 59.81 m³/h Pressure drop 48.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 275.59 not rated not rated not rated not rated not rated
40 451.50 275.24 not rated not rated not rated not rated
45 622.82 449.89 274.94 not rated not rated not rated
50 792.64 620.06 448.55 274.82 not rated not rated
55 961.76 788.77 617.76 447.60 274.95 not rated
60 1130.50 956.81 785.54 616.07 447.21 275.47

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 212.53 not rated not rated not rated not rated not rated
40 344.89 212.00 not rated not rated not rated not rated
45 473.62 343.22 211.66 not rated not rated not rated
50 601.15 470.92 342.02 211.49 not rated not rated
55 728.15 597.46 468.92 341.19 211.56 not rated
60 854.85 723.49 594.71 467.49 340.84 211.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 451.500 78.31 78.2
Low speed (Y) 344.889 59.81 48.5

Dimensions

Dimension drawing of BC/BD-2x680FC5-B03 C
Dimension drawing
Dimensions as drawn
A 11050 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 2310 mm
K 11550 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11550 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.