Skip to Content

Dry cooler BC/BD-2x691EB1-B04 C

Dry cooler BC/BD-2x691EB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x691EB1-B04 C

Heat rejection i
693.96 kW
Air flow
287,289 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 287,289 m³/h
External surface 1,729.7 m²
Inner volume 271.4 dm³
Fin materialAluminium
Net weight 1,919 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 102.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2x691EB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
693.955 kW Fluid flow 120.43 m³/h Pressure drop 33.7 kPa
Heat rejection · Low speed (Y)
558.826 kW Fluid flow 96.99 m³/h Pressure drop 22.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 383.21 not rated not rated not rated not rated not rated
40 693.96 387.21 not rated not rated not rated not rated
45 998.57 696.40 390.75 not rated not rated not rated
50 1301.17 999.73 698.80 393.97 not rated not rated
55 1602.93 1301.14 1001.09 701.15 397.06 not rated
60 1904.14 1601.78 1301.58 1002.73 703.68 400.08

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 311.26 not rated not rated not rated not rated not rated
40 558.83 314.58 not rated not rated not rated not rated
45 800.45 560.75 317.46 not rated not rated not rated
50 1040.21 801.35 562.58 320.11 not rated not rated
55 1279.11 1040.11 802.36 564.53 322.67 not rated
60 1517.47 1278.10 1040.38 803.71 566.68 325.28

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 693.955 120.43 33.7
Low speed (Y) 558.826 96.99 22.8

Dimensions

Dimension drawing of BC/BD-2x691EB1-B04 C
Dimension drawing
Dimensions as drawn
A 8950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1400 mm
I 2310 mm
K 9450 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 9450 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.