Skip to Content

Dry cooler BC/BD-2x780AB1-B01 C

Dry cooler BC/BD-2x780AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x780AB1-B01 C

Heat rejection i
632.71 kW
Air flow
246,519 m³/h
Fans
14 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 246,519 m³/h
External surface 1,729.7 m²
Inner volume 243.6 dm³
Fin materialAluminium
Net weight 2,002 kg
Fans
Quantity 14
Diameter 800 mm
Speed 900 rpm
Power 25,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2x780AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
632.706 kW Fluid flow 109.82 m³/h Pressure drop 33.6 kPa
Heat rejection · Low speed (Y)
511.324 kW Fluid flow 88.74 m³/h Pressure drop 22.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 350.67 not rated not rated not rated not rated not rated
40 632.71 354.32 not rated not rated not rated not rated
45 908.62 634.88 357.53 not rated not rated not rated
50 1182.65 909.60 636.93 360.49 not rated not rated
55 1455.75 1182.53 910.70 639.01 363.28 not rated
60 1728.34 1454.59 1182.76 912.12 641.30 366.14

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 285.83 not rated not rated not rated not rated not rated
40 511.32 288.69 not rated not rated not rated not rated
45 731.07 512.78 291.15 not rated not rated not rated
50 948.96 731.37 514.14 293.47 not rated not rated
55 1165.97 948.23 731.83 515.58 295.66 not rated
60 1382.49 1164.27 947.88 732.63 517.26 297.94

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 632.706 109.82 33.6
Low speed (Y) 511.324 88.74 22.8

Dimensions

Dimension drawing of BC/BD-2x780AB1-B01 C
Dimension drawing
Dimensions as drawn
A 8950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1200 mm
I 2310 mm
K 9450 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8950 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.