BC/BD-2x780DC1-B03 C
440.17 kW
Defrost: None
Product code: BC/BD-2x780DD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 97,838 m³/h |
|---|---|
| External surface | 2,736.5 m² |
| Inner volume | 509.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,331 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 4,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x780DD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 274.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 439.76 | 274.10 | not rated | not rated | not rated | not rated |
| 45 | 600.67 | 438.76 | 274.22 | not rated | not rated | not rated |
| 50 | 760.10 | 598.88 | 438.21 | 274.61 | not rated | not rated |
| 55 | 918.84 | 757.55 | 597.76 | 438.23 | 275.40 | not rated |
| 60 | 1077.21 | 915.56 | 755.90 | 597.48 | 438.98 | 276.68 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | not rated | not rated | not rated | not rated |
| 50 | not rated | not rated | not rated | not rated | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | not rated | not rated |
| 60 | not rated | not rated | not rated | not rated | not rated | 201.57 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 439.755 | 76.28 | 94.2 |
| Low speed (Y) | — | — | — |
| A | 8750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 9050 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 9050 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.